Smoke Detector Testing and Sensitivity Data
For Smoke Detectors Sold By Siemens
Siemens can be reached at 1-800-268-6831 Ext. 4202
Smoke Detector Model For Sale Now for New Installation Tester Model Number Measurement Value or Confirmation Within Range Tester Availability and Delivery Time to Third Party Where Available
DIZ-3 No Reports Sensitivity on Control Panel for IXL control panel or via TM-I3 for INS-2 control panel Reports Sensitivity Value Yes
DIZ-A3
DIZ-B3
DI-AX3 No Reports Snesitivity on  XL-3 Control Panel Reports Sensitivity Value N/A
DI-BX3
DI-X3
DP-3X
PEX-3000
PEX-3000T
PEZ-3 No Reports Sensitivity on Control Panel for IXL control panel or via TM-P3 for INS-2 control panel Reports Sensitivity Value Yes
PEZ-3T
ID-60A Yes Reports Sensitivity on MXL Control Panel Reports Sensitivity Value N/A
ID-60B
ID-60I
ID-60IA
ID-60IAC
ID-60IB
ID-60IBC
ID-60IC
ID-60P
ID-60PT
ILI-1Ac
ILI-1Bc
ILI-1C
ILP-1
ILP-2
ILPT-1
FP-11
FPT-11
DP-4 No MG 7/9 Reports Sensitivity Value Yes 8-12 Wks
DP-6
F930 Yes MG 7/9 Reports Sensitivity Value Yes 8-12 Wks
F936
R716H
R902
R930
R-930
R935
RT716H
DI-2 No SCU-9 with Adapter for head is obsolete and no longer available Reports Sensitivity Value Not Available Obsolete
DI-2D
F3
F3/5A
F4
F5
F5A
F5B
DI-4 Yes SCU-9 & SAU-4 or MG 7/9 Reports Sensitivity Value Yes Model MG7/9          8-12 Wks
DI-6
DI-4A No
DI-4AIS
DI-4B
PE-11 Yes Self-Diagnostic No N/A
PE-11C
PE-11T
DI-3 Yes TM-I3 Reports Sensitivity Value Yes 6-8 wks, Digital Volt Meter Not Included
DI-3C
DI-3IS
DI-A3
DI-B3 No
DP-3 No TM-DP3 Reports Sensitivity Value Yes 6-8 Wks, Digital Volt Meter Not Included
PE-3
PE-3000 No TM-P3000 is Obsolete and no Longer Available Reports Sensitivity Value Not Available Obsolete
PE-3000T
PEC-3 No TM-P3 Reports Sensitivity Value Yes 6-8 Wks, digital Volt Meter Not Included
PEC-3T
Smoke Detector Model For Sale Now for New Installation Tester Model Number Measurement Value or Confirmation Within Range Tester Availability and Delivery Time to Third Party Where Available
   
NOTES  
1. All detectors can be functionally tested using smoke or by using an aerosol approved or recognized as acceptable for use by Seimens.
2. Sensitivity meters are available to Qualified 3rd parties only.
3. Price of TM-I3, TM-P3, TM-DP3 and TM-PE3 does not include the required Digital Volt Meter.
4. For current availability and costs of testing meters, contact the manufacturer.
 
Detector Sensitivity Chart
Siemens, Cerberus, Pyrotronics Dec: 1, 2003
Models Volts D.C. Stand-by Current uA Alarm Current mA Max.  Volts D.C. Min.   Volts D.C. Obscuration   
% / ft
DI-B3,
DIZ-3,
DIZ-A3,
DIZ-B3
      5.6 2.9 1.2(+0.2 / -0.9)
PEX-3000, PEX-300T       3.62 1.62 3.0(+0.61 / -2.2)
ID-60I,
ID-60IC,
ILI-1C
      5 1.5 1.5(+0.2 / 0.9)
ID-60IB       4.8 2 1.2(+0.2 / -0.5)
ID-60IA       3.8 1.5 0.9(+0.3 / -0.4)
ID-60P       3.62 1.62 3.0(+0.6 / -2.2)
ILP-1,
ILP-2,
ILPT-1
      3.62 1.62 3.0(+1.0 /-2.2)
FP-11           3.0(+0.61 / -2.37)
DI-4A       6.1 3.2  
DI-3C,
DI-3IS
      5.8 2.5 1.5(+0.2 / -0.9)
DI-A3       5 2 0.9(+0.3 / -0.4)
DI-X3       4 1.8  
PE-3       9.5 2.2 3.0(+0.2 / -2.0)
PE-11C, PE-11T           2.0(+0.64 / -1.37)
PEX-3000       3.62 1.62 3.0(+0.6 / -2.2)
F-930 21 60 100      
R-930 21 130 100      
DP-4,
DP-6,
DI-4,
DI-4B
21 100 150      
DI-6 21 100 100