This page is part of the official website of the Canadian Fire Alarm Association. If you arrived to this page directly from an internet  search engine, you may wish to visit our home page and site map at www.cfaa.ca
SMOKE DETECTOR TESTING DATA
For Smoke Detectors Sold By Simplex
As of 1/14/2004
Simplex Detectors
Smoke Detector Model Type For Sale Now, New Installation Measurement value % Obscuration Units Volts mA Other Only Confirmation within range Tester Model Number Tester Available for Purchase Functional test by Aerosol Notes
2098-9560 Ionization No Yes .55 - 2.04% Voltage No 10 Megohm impedance voltmeter Yes Yes Exact sensitivity range is located on head
2098-9602 Photoelectric No Yes 1.0 - 2.7% Voltage No 10 Megohm impedance voltmeter Yes Yes Exact sensitivity range is located on head
2098-9604 Phot with heat No Yes 1.0 -2.7% Voltage No 10 Megohm impedance voltmeter Yes Yes Exact sensitivity range is located on head
2098-9201C Photoelectric No Yes 1.5 - 3.6% Obsc. No Gemini 501A Yes Yes  
2098-9202C Photo with heat No Yes 1.5 - 3.6% Obsc. No Gemini 501A Yes Yes  
2098-9576, 2098-9130 Ionization No Yes .8 - 1.8% Obsc. No Gemini 501A Yes Yes  
2098-9544 Ionization No Yes .8 - 1.5 % Obsc. No Gemini 501A Yes Yes  
12098-9505 Ionization No Yes .8 - 1.5% Obsc. No Gemini 501A Yes Yes  
2098-9636 Photoelectric No Yes 1.0 3.4% Obsc. No Gemini 501A Yes Yes  
12098-9605 Ionization No Yes .2 - 3.4 MIC No TSI-A100 Yew Yes  
12098-9610 Ionization No Yes .2 - 3.4 MIC No TSI-A100 Yes Yes Voltage range is printed on the head
2098-9642 Ionization No Yes 1.0 - 3.4% Obsc. No Gemini 501A or HochikiTSA-B110 Yes Yes  
2098-9577 Ionization No Yes .9 - 1.8% Voltage No Mod 400R Yes Yes  
2098-9110 Ionization Yes Yes 1.5% Obsc. No Mod 400R Yes Yes  
12098-9515   No Yes     No Meter not available No Yes  
4098-9601C Photoelectric Yes No 3.0% Obsc. Yes 553-810 Yes Yes  
4098-9602C Photoelectric Yes No 3.0% Obsc. Yes 553-810 Yes Yes  
4098-9603C Ionization Yes Yes 1.3% Obsc. No 553-832 Yes Yes