SMOKE DETECTOR TESTING DATA Revision Changes shown in RED Feb 11/2002
For Smoke Detectors Sold By System Sensor Canada Rev 3: Nov 4/02
System Sensor Canada can be reached at 1-800-736-7672
Series Smoke Detector Model #    (1) For Sale Now New Insatallation  (2) Tester Model Number Per Instruction Sheet       (3) Measurement Value % Osc. Or Voltage     (4) Sensitivity Range Only Confirmation Within Range        (5) Tester Available For Purchase     (6) Approx. Delivery Time             (7) Approx. Cost to 3rd Party             (8) Functional Testing by Aerosal                     (9) Functional Testing By Smoke          (10)  
    Yes or No   Yes or No   Yes or No Yes or No Weeks $ Yes or No Yes or No
100 1151A Yes MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2151A Yes MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2100A No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2100TA No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2112/24BA No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2112/24TBA No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2100SA No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2100TSA No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2112/24SA No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2112/24TSA No MOD400R Yes see note 3 No Yes 2 to 3 300 Yes as per Note 2 Yes
  2100TRA No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2112/24TRA No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2100ATA No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2112/24ATA No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2112/24ATRA No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2112/24AITRA No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  DH100PA No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  DH100ACDCIA Yes MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  DH100ACDCPA No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  DH100LPA Yes MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  DH100ACDCLPA Yes MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
                       
200 1251A No  See Note 1  See Note 1   No See Note 1     Yes as per Note 2 Yes
  2251A No  See Note 1  See Note 1   No See Note 1     Yes as per Note 2 Yes
  2251TA No  See Note 1  See Note 1   No See Note 1     Yes as per Note 2 Yes
  2251TMA No  See Note 1  See Note 1   No See Note 1     Yes as per Note 2 Yes
  3251A No  See Note 1  See Note 1 see note 3 No See Note 1     Yes as per Note 2 Yes
  1251BA No  See Note 1  See Note 1   No See Note 1     Yes as per Note 2 Yes
  2251BA No  See Note 1  See Note 1   No See Note 1     Yes as per Note 2 Yes
  2251TBA No  See Note 1  See Note 1   No See Note 1     Yes as per Note 2 Yes
  2251TMBA No  See Note 1  See Note 1   No See Note 1     Yes as per Note 2 Yes
  7251A Yes  See Note 1  See Note 1   No See Note 1     Yes as per Note 2 Yes
  FTX-P1A Yes  See Note 1  See Note 1   No See Note 1     Yes as per Note 2 Yes
  DH200PA Yes  See Note 1  See Note 1   No See Note 1     Yes as per Note 2 Yes
  DH200RPA Yes  See Note 1  See Note 1   No See Note 1     Yes as per Note 2 Yes
                       
400 1451A Yes MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2451A Yes MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  1400A Yes MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  1412A Yes MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  1424A Yes MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2400A Yes MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2400THA Yes MOD400R Yes see note 3 No Yes 2 to 3 300 Yes as per Note 2 Yes
  2412BA Yes MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2424A Yes MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2424THA Yes MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  DH400A No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  DH400ACDCA No MOD400R Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
500 1551AB No MOD400R(See Note 1) Yes   No Yes 2 to 3 300 Yes as per Note 2 Yes
  2551AHR No MOD400R(See Note 1) Yes & See Note 1 see note 3 No Yes 2 to 3 300 Yes as per Note 2 Yes
  2551TAHR No MOD400R(See Note 1) Yes & See Note 1   No Yes 2 to 3 300 Yes as per Note 2 Yes
800 1800 No TM80 Yes   No No     Yes as per Note 2 Yes
  1806 No TM-80 Yes   No No     Yes as per Note 2 Yes
  1812 No TM-80 Yes   No No     Yes as per Note 2 Yes
  1824 No TM-80 Yes   No No     Yes as per Note 2 Yes
  1800EC No TM-80 Yes   No No     Yes as per Note 2 Yes
  1851B No TM-80 Yes   No No     Yes as per Note 2 Yes
  2800-A No TM-80 Yes   No No     Yes as per Note 2 Yes
  2851B-A No TM-80 Yes   No No     Yes as per Note 2 Yes
                       
i3 C2W-BA Yes CSENS-RDRA Yes 1 TO 4%/FT No Yes 2 to 3 300 Yes as per Note 2 Yes
  C2WT-BA Yes CSENS-RDRA Yes 1 TO 4%/FT No Yes 2 to 3 300 Yes as per Note 2 Yes
  C4W-BA Yes CSENS-RDRA Yes 1 TO 4%/FT No Yes 2 to 3 300 Yes as per Note 2 Yes
  C4WT-BA Yes CSENS-RDRA Yes 1 TO 4%/FT No Yes 2 to 3 300 Yes as per Note 2 Yes
  C2WTA-BA Yes CSENS-RDRA Yes 1 TO 4%/FT No Yes 2 to 3 300 Yes as per Note 2 Yes
  C2WTR-BA Yes CSENS-RDRA Yes 1 TO 4%/FT No Yes 2 to 3 300 Yes as per Note 2 Yes
  C4WTA-BA Yes CSENS-RDRA Yes 1 TO 4%/FT No Yes 2 to 3 300 Yes as per Note 2 Yes
  C4WTR-BA Yes CSENS-RDRA Yes 1 TO 4%/FT No Yes 2 to 3 300 Yes as per Note 2 Yes
  C4WTAR-BA Yes CSENS-RDRA Yes 1 TO 4%/FT No Yes 2 to 3 300 Yes as per Note 2 Yes
  C4WITAR-BA Yes CSENS-RDRA Yes 1 TO 4%/FT No Yes 2 to 3 300 Yes as per Note 2 Yes
Notes
1. Series 200 and 500 devices addressable, intelligent sensors also have their sensitivity displayed at the control panel as a value determined by the panel manufacturor.
    Early versions of some models of the 200 series devices were manufactured with a MOD400R test port. Present 200 series versions do not have a MOD400R test port.
2. The only accepted Aerosal Test Product accepted by System Sensor is Home Safegaurd 25S Gas with 1490 Adapter Tube.
3. The MOD400R sensitivity range is printed on the ULC name plate label affixed to the back of each detector. The range is expressed in VDC on a voltmeter used in conjunction with the MOD400R.