SMOKE DETECTOR TESTING DATA

For Smoke Detectors sold by Edwards and Mirtone

tech.services.canada@ge.com

Table 1

Smoke Detector Availability as of December 2003

SMOKE DETECTOR TESTING DATA

Smoke Detectors sold by Edwards and Mirtone

Smoke Detector Model

Estimated Selling Period (new)

For Sale Now in New Installation

Tester Model Number

Measurement Value or Operational Confirmation

Tester Availability and Delivery Time to 3rd Party Where Available.

73741

No

N/A

N/A

N/A

301, 303

Pre-1977

No

N/A

N/A

N/A

DIS-3/5A, DIS-5B, DIA-9,

Pre-1977

No

SCU-7

Value

N/A

6400, 6402

Pre-1977

No

SCU-8

Value

N/A

SCU-9

N/A

6450, 6450-1, 6480-500

1977 1980

No

6497

Value

N/A

6349, 6350, 6380-500

73403, 73402

1980 1983

No

TM79, TM80

Value

N/A

1977 1991

TM79, TM80

N/A

6249C,6250C,

6269C,6269C-001, 6270C,6270C-001,

6264C-001, 6266C-001,

6264C-005, 6265C-002,

6266C-002, 6269C-003,

6270C-003

 

 

 

1983 to 2003

 

 

 

No

6257

 

 

 

Value

N/A

6277

N/A

6277-A

Yes

4-8 Weeks

73494, 73495,

73575, 73595,

73584, 73405-001,

73441, 73594-001,

73576, 73596

 

 

1983 to 2003

 

 

No

6257

 

 

Value

N/A

6277

N/A

6277-A

Yes

4-8 Weeks

6250C-100, 6250C-200,

6264C-100, 6266C-200

6270C-200

1991 to 2003

 

No

Reports Sensitivity on Control Panel

 

Value

 

N/A

GSA-IS, SIGA-IS

GSA-PS, SIGA-PS,

GSA-PHS, SIGA-PHS,

SIGA-IPHS, SIGA-IPHSB

 

1994 to Present

 

Yes

 

Reports Sensitivity on Control Panel

 

Value

 

N/A

C2M-4PD, C2M-4PDH,

C2M-PD, C2M-PDC,

C2M-PDHC, C2M-PDHRC,

CM2M-PD, CM2M-PDH,

CM2M-PDHC,

CM2M-PDHRC

 

 

2000 to Present

 

 

Yes

 

 

Magnet Test

 

 

Optical

 

 

N/A

EDW1400A, EDW2400A,

EDW1451A, EDW2451A,

EDW 1151A, EDW2151A

MT1400A, MT2400A,

MT1451A, MT2451A,

MT1151A, MT2151A,

 

 

2000 to Present

 

 

Yes

 

 

MOD-400R

 

 

Value

 

 

Yes

From System Sensor

1551F, 2551F, 2551AHR,

 

1991 to Present

No

Reports Sensitivity on Control Panel

N/A

N/A

71551, 71552

No

Reports Sensitivity on Control Panel

N/A

N/A

1251A, 2251A

2001 to Present

Yes

Reports Sensitivity on Control Panel

N/A

N/A

DH400ACDCI,

2851B

No

System Sensor

N/A

N/A

DH500F c/w 2551F

1992 to 2001

No

Reports Sensitivity on Control Panel

Value

Yes

From System Sensor

DH200PA

2001 to Present

Yes

Reports Sensitivity on Control Panel

Value

N/A

7251A

2001 to Present

Yes

Reports sensitivity on Control Panel

Value

N/A

EC10U, EC30-U

2003

Yes

C-PST

Value

Yes

Spring 2004


 

 

Table 2

Compiled Data for all current Edwards/ Mirtone Smoke Detectors

Detector

Sensitivity Setting

Obsuration

(in %/foot)

Range

Analog Detectors

Fire panel

Trouble

Normal

Maintenance

Alert

Alarm

 

6250C-100/-200

 

ESA2000

1

0.90

00-07

08-123

124-129

130-255

2

0.93

00-07

08-123

124-135

136-255

3

0.96

00-07

08-129

130-141

142-255

4

1.02

00-07

08-135

136-147

148-255

5

1.22

00-07

08-141

142-154

155-255

 

6270C-100/200

 

ESA2000

1

0.98

00-10

11-89

90-99

100-255

2

1.15

00-10

11-89

90-105

106-255

3

1.35

00-10

11-99

100-114

115-255

4

1.55

00-10

11-105

106-123

124-255

5

1.65

00-10

11-114

115-129

130-255

 

6264C-200

 

ESA2000

1

1.01

00-07

08-164

165-169

170-255

2

1.05

00-07

08-164

165-171

172-255

3

1.14

00-07

08-169

170-173

174-255

4

1.16

00-07

08-171

172-175

176-255

5

1.19

00-07

08-173

174-179

180-255

 

6266C-200

 

ESA2000

1

1.20

00-10

11-89

90-99

100-255

2

1.55

00-10

11-89

90-105

124-255

3

2.05

00-10

11-99

100-114

146-255

4

2.60

00-10

11-105

106-123

172-255

5

3.15

00-10

11-114

115-129

195-255

 

1551F

 

IRC3 / FCC

1

Most Sensitive

400

520-1440

1550

1710

2

Normal Sens.

400

520-1440

1550

1940

3

Less Sensitive

400

520-1440

1550

2170

4

Least Sensitive

400

520-1440

1550

2390

 

2551F

 

ICR3 / FCC

1

Most Sensitive

400

600-1200

1550

1810

2

Normal Sens.

400

600-1200

1550

1940

3

Less Sensitive

400

600-1200

1550

2010

4

Least Sensitive

400

600-1200

1550

2110

1251A, 1551F

 

EST3

Most Sensitive

400

600-1200

1650

1500

Normal

400

600-1200

1650

1562

Least Sensitive

400

600-1200

1650

1625

2251A, 2551F, 2551TF

 

EST3

Most Sensitive

400

520-1400

1550

1745

Normal

400

520-1400

1550

2050

Least Sensitive

400

520-1400

1550

2355

 

7251A

 

EST3

Most Sensitive

150

750-900

525

1600

More Sensitive

150

750-900

525

1800

Normal

150

750-900

525

2100

Less Sensitive

150

750-900

525

2500

Least Sensitive

150

750-900

525

2900

SIGA-IPHS,

SIGA-IPHSB

 

EST2, EST3, IRC3, QuickStart

Most Sensitive

1.0

0

<80

80

100

More Sensitive

2.0

0

<80

80

100

Normal

2.5

0

<80

80

100

Less Sensitive

3.0

0

<80

80

100

Least Sensitive

3.5

0

<80

80

100

SIGA-PHS,

 

EST2, EST3, IRC3, QuickStart,

Most Sensitive

1.0

0

<80

80

100

More Sensitive

2.0

0

<80

80

100

Normal

2.5

0

<80

80

100

Less Sensitive

3.0

0

<80

80

100

Least Sensitive

3.5

0

<80

80

100

SIGA-PS

 

EST2, EST3, IRC3,

QuickStart

Most Sensitive

1.0

0

<80

80

100

More Sensitive

2.0

0

<80

80

100

Normal

2.5

0

<80

80

100

Less Sensitive

3.0

0

<80

80

100

Least Sensitive

3.5

0

<80

80

100

SIGA-IS

 

EST2, EST3, IRC3, QuickStart

Most Sensitive

0.7

0

<80

80

100

More Sensitive

1.0

0

<80

80

100

Normal

1.2

0

<80

80

100

Less Sensitive

1.4

0

<80

80

100

Least Sensitive

1.6

0

<80

80

100

GSA-PHS

 

MIR2

Most Sensitive

1.0

0

<80

80

100

More Sensitive

2.0

0

<80

80

100

Normal

2.5

0

<80

80

100

Less Sensitive

3.0

0

<80

80

100

Least Sensitive

3.5

0

<80

80

100


Smoke Detector /

Fire Panel

Sensitivity Setting

Obscuration

(% per foot)

Range

Analog Detectors

Fire panel

Trouble

Normal

Maintenance Alert

Alarm

GSA-PS

 

MIR2

Most Sensitive

1.0

0

<80

80

100

More Sensitive

2.0

0

<80

80

100

Normal

2.5

0

<80

80

100

Less Sensitive

3.0

0

<80

80

100

Least Sensitive

3.5

0

<80

80

100

GSA-IS

 

MIR2

Most Sensitive

0.7

0

<80

80

100

More Sensitive

1.0

0

<80

80

100

Normal

1.2

0

<80

80

100

Less Sensitive

1.4

0

<80

80

100

Least Sensitive

1.6

0

<80

80

100

 

DH500 c/w 2551F

 

IRC3 / FCC

1

Most Sensitive

400

600-1200

1550

1810

2

Normal Sens.

400

600-1200

1550

1940

3

Less Sensitive

400

600-1200

1550

2010

4

Least Sensitive

400

600-1200

1550

2110

DH200PA

 

EST3

Least Sensitive

400

520-1400

1550

1745

Normal

400

520-1400

1550

2050

Most Sensitive

400

520-1400

1550

2355

 

 

Conventional Detectors

 

Sensitivity Setting

 

Obscuration

(% per foot)

 

Range

 

EC30U-3

Factory set sensitivity - not adjustable

<1.38

Failed

1.38 to 3.08

Acceptable

>3.08

Failed

EDW1151A, EDW1400A, EDW1451A

Factory set sensitivity - not adjustable

1.5 nominal

Measure with the MOD-400R and compare with measurement recorded on the detector label.

EDW2112A, EDW2400A, EDW2451A

Factory set sensitivity - not adjustable

1.4

Measure with the MOD-400R and compare with measurement recorded on the detector label.

C2M-4PD, C2M-4PDH, C2M-PD, C2M-PDC,

C2M-PDHC, C2M-PDHRC,

CM2M-PD, CM2M-PDC, CM2M-PDHC, CM2M-PHC

CM2M-PDHRC

Factory set sensitivity - not adjustable Determined by number of flashes of LED with magnet test.

0

1 Flash

Unserviceable

4.35

2 Flashes

Above Acceptable range

3.83

3 Flashes

Above acceptable range

2 to 3.5

4 7 Flashes

Acceptable

1.85

8 Flashes

Below acceptable range

1.35

9 Flashes

Below acceptable range

6249C, 6250C
Note 1

73494, 73495

Maximum

0.5

0.31Vdc

Minimum

1.0

4.20Vdc

6264C-001 Note 1

73405

Maximum

0.58

0.90Vdc

Minimum

1.0

4.20Vdc

6264C-005 Note 1

Maximum

0.71

3.10Vdc

Minimum

2.08

5.20Vdc

6266C-001 Note 1

73594,

Maximum

0.50

0.031Vdc

Minimum

4.0

3.5Vdc (manufactured after 01/01/91)

6269C, 6270C
Note 1

73595, 73575

Maximum

0.65

0.031Vdc

Minimum

2.0

0.20Vdc (manufactured after 01/01/91)

 

 

Note 1- Extracted from 6277-A test set operating instructions Table 1.